二次绕组之间及剩余电压绕组对地工频耐压一分钟通过3 KV(r.m.s), 通过。
Secondary winding and residual
voltage winding to ground frequency withstand voltage one minute through 3kv
(r.m.s) , Pass.
补偿电抗器绕组末端对地工频耐压试验一分钟通过10KV(r.m.s), 通过。
Compensation Reactor winding end to ground frequency
withstand voltage test one minute through 10 KV (r.m.s) , Pass.
阻尼回路直流电阻测量: 5.0 Ω
DC resistance measurement of damping
loop: 5.0
载波耦合装置保护间隙的工频放电电压不大于2KV(r.m.s),(间隙0.5mm左右)
The power frequency discharge
voltage of the carrier coupling device protection gap is not more than 2 kv
(r.m.s) , (gap is about 0.5 mm)
变压器油:油号DB-45平均击穿电压 > 40KV , 通过。
Transformer oil: No. DB-45 average
breakdown Voltage > 40KV, Pass.
4、 误差试验Error Test
天气:晴Weather: Sunny
室温: 22 ℃ Room temperature: 22 °C
调节绕组联接方式
Regulating winding connection
X0——X13X11——X22X23——L23L22——L12L13——L0
输 出
端子Output Terminal
负 荷 方 式 VA
cosΦ=0.8 (滞后)
80℅ Un
100℅ Un
120℅ Un
比值差
相角差
比值差
相角差
比值差
相角差
a n
da dn
f(℅)
δ(’)
f(℅)
δ(’)
f(℅)
δ(’)
a n
140
━━
-0.26
+14
-0.26
+10
-0.27
+12
35
━━
+0.32
+3
+0.33
+4
+0.33
+5
5℅ Un
100℅ Un
190℅ Un
f(℅)
δ(’)
f(℅)
δ(’)
f(℅)
δ(’)
da dn
━━
140
+0.40
+32
-0.20
+14
-0.82
+12
━━
35
+0.30
+22
+0.55
+8
+0.78
+42
07
17
2025
LVQB-35W2/200/5户外35六氟化硫互感器 35KVD电流互感器 祝捷电气