              conventional  fire  alarm    control  panel    


The  Panel  is  a  4-zone  to  16-zone  FACP  (Fire  Alarm  Control  Panel),  which  uses
conventional  input  devices.  The  panel  accepts  water  flow  devices,  two-wire
smoke  detectors,  four-wire  smoke  detectors,  pull  stations  and  other
normally-open  contact  devices.  Outputs  include  four  Notification  Appliance
Circuits  (NAC,  SOUND1-4),  three  standard  Form-A  relays  (alarm,  trouble  and
supervisory)  and  an  EIA-485  port  to  interface  with  remote  annunciators  and
optional  remote  relay  modules.  The  FACP  is  field  programmable  via  the  panel
keypad.  It  also  supervises  all  wiring,  AC  voltage  and  battery  level.
This  series  of  panels  are  basically  the  same  in  application  and  operation,  their
differences  are  shown  in  Table  1-1.  The  Panel  will  be  described  as  the  example  in
the  following  sections.
Table  1-1
FACP  Number  of
Detection  Zones
Number  of
Sounder  Outputs
Output  Delay
Settings
ZONE-4  4  1  N/A
ZONE-8  8  2  N/A
ZONE-16  16  4  N/A
1.1  Product  Features
l  4,8,16  Class  B  Initiating  Device  Circuits  (IDCs)
?  All  zones  accept  conventional  detectors  and  any  normally  open
contact  device
l  Four  Class  B  Notification  Appliance  Circuits  (NACs)
l  One  Form-A  Alarm  Relay
l  One  Form-A  Trouble  Relay
l  One  Form-A  Supervisory  Relay
l  3.0  amps  of  system  power
l  Max  20  conventional  detectors  in  one  zone.
l  Auto/Manual  mode  setting  enable  walk  test.
l  Each  Zone  can  be  disabled,
l  Sound  output  can  be  disabled.
l  Manual  active  sound  output  enabled.
AC  Power
90  to  270  VAC,  50  /60  Hz,  2.3  amps
Wire  size:  minimum  #14  AWG  (2.0  mm2)  with  600V  insulation
Battery  (lead  acid  only)
Maximum  Charging  Circuit:  Normal  Flat  Charge—27.6V  @  0.8  amp
Maximum  Charger  Capacity:  18  Amp  Hour  batter
Sound  Output  Device  Circuits
General  Alarm  Zones  1  through  16
Operation:  All  zones  Class  B
Normal  Operating  Voltage:  Nominal  24  VDC  (ripple  =  100  mV  maximum)
Alarm  Current:  15  mA  threshold
Short  Circuit  Current:  42  mA  maximum
Maximum  Loop  Resistance:  100  ohms
End-of-Line  Resistor:  4.7K,  ½  watt
Detector  Loop  Current  is  sufficient  to  ensure  operation  of  two  alarmed  detectors
per  zone
Standby  Current:  7.26  mA
Three  Relays  Output
Relay  contact  rating:  2.0  amps  @  30  VDC  (resistive),  2.0  amps  @  30  VAC
(resistive)
Nonresettable  24  VDC  Power
Maximum  ripple  voltage:  10  mVRMS  Operating  Voltage  nominal  24  volts
Total  DC  current  available  from  this  output  is  up  to  500  mA
Recommended  maximum  Standby  current  is  150  mA